บริษัท ทริปเปิ้ล อี เทรดดิ้ง จำกัด

EP MVS CB 1000A 50kA 3P MDO ETV6 drawout manual Circuit breaker MVS10N3MW6V

฿88200.00
EasyPact MVS10 is a 1000A circuit breaker. The application is suitable for 690VAC@50/60Hz. With manually operating mechanism(ACB/SD), and basic trip unit with display. The breaking capacity(Icu) is 50
เหลือ 100 ชิ้น
ซื้อเลย
หยิบลงตะกร้า
  • หมวดหมู่ : SCHNEIDER
  • รหัสสินค้า : sc-00090

รายละเอียดสินค้า EP MVS CB 1000A 50kA 3P MDO ETV6 drawout manual Circuit breaker MVS10N3MW6V

Main
RangeEasyPact
Product nameMVS10N
Device short nameMVS10N
Product or component typeCircuit breaker
Device applicationDistribution
Poles description3P
Protected poles description3P 3d
[In] rated current1000 A at 40 °C
Network typeAC
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory B
Trip unit nameETV6G
Trip unit technologyElectronic
Trip unit rating1000 A
Complementary
Network frequency50/60 Hz
Control typeManually operated
Mounting modeDrawout
Mounting supportRail
Base plate
Connection positionVertical
Horizontal
Location of connectionRear
[Ui] rated insulation voltage1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage12 kV conforming to IEC 60947-2
Circuit breaker CT rating1000 A
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability20000 cycles (with maintenance) conforming to IEC 60947-2
10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durabilityCategory B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Connection pitch115 mm without spreader
Contact position indicatorYes
[Icm] rated short-circuit making capacity105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit protection functionsLSIG
Protection typeShort time short-circuit protection
Earth fault
Overload protection (long time)
Instantaneous short-circuit protection
Fault indicationEarth fault
Overload
Short-circuit
Internal fault
Long time pick-up adjustment type IrAdjustable 9 settings
Long time pick-up adjustment range0.4...1 x In
Long time delay adjustment typeAdjustable 9 settings
[tr] long-time delay adjustment range0.5…24 s at 6 x Ir
Short-time pick-up adjustment type IsdAdjustable 9 settings
[Isd] short-time pick-up adjustment range1.5...10 x Ir
Short-time delay adjustment typeAdjustable 5 settings
[tsd] short-time delay adjustment range100…400 ms
Instantaneous pick-up adjustment type IiAdjustable 9 settings
Instantaneous pick-up adjustment range2...15 x In
Off
Ground-fault pick-up adjustment typeAdjustable 9 settings
Ground-fault time delay adjustment type -tgAdjustable 5 settings
[tg] ground-fault time delay adjustment range100…400 ms
[Ig] ground-fault pick-up adjustment range0.2...1 x In
Zone selective interlocking ZSIWith
Display typeDigital display
Type of measurementVoltage
Current sensor rating range400/2000 A
Maximum breaking time25 ms
Maximum closing response time70 ms
Height439 mm
Width441 mm
Depth395 mm
Net weight70 kg
Environment
StandardsIEC 60947-2
Product certificationsGOST
CCS
IEC
CCC
Pollution degree4 conforming to IEC 60664-1
IP degree of protectionIP40
Ambient air temperature for operation-5…70 °C
Ambient air temperature for storage-40…85 °C without control unit
-25…85 °C with control unit
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height42.0 cm
Package 1 Width35.0 cm
Package 1 Length50.0 cm
Package 1 Weight38.0 kg
Contractual warranty
Warranty18 months